ꁆ ꁇ

Inverter Commercial Unit

Contact Us
Model: JRG-BYRBD83.0D,JRG-BYRBD165.0D
Product Features:
1. Suitable for heating / hot‑water projects with fluctuating loads and precise temperature‑control requirements
2. No requirement for water‑tank size
3. Excellent energy efficiency under low‑temperature operating conditions

Application: Hot water for hotel guest rooms, clubs and bath centers (with large water‑consumption differences among morning, noon and evening); heating for office buildings

Unit Parameters

JRG-BYRBD83.0D

JRG-BYRBD165.0D

Rated Heating Capacity (7/6℃, −/45℃)

83.00kW

165.00kW

Rated Heating Input Power

24.13kW

48.10kW

Rated Heating COP

3.44

3.43

Rated Cooling Capacity (35/−℃/7℃)

65kW

130.00kW

Rated Cooling Input Power

23.13kW

46.26kW

Rated Cooling EER

2.81

2.81

Cooling Seasonal Performance Factor (CSPF)

4.37

4.36

Nominal Heating Capacity (−12/−13.5℃/41℃)

57.00kW

110.00kW

Nominal Heating Input Power

22.26kW

43.14kW

Nominal Heating COP

2.56

2.55

Lowtemperature Heating Capacity (−20℃/41℃)

49.00kW

95.00kW

Lowtemperature Heating Input Power

22.90kW

44.60kW

Lowtemperature Heating COP

2.14

2.13

Fancoil Type Heating Seasonal Performance Factor (HSPF)

3.21

3.20

Fancoil Type Annual Performance Factor (APF)

3.32

3.31

Power Supply Specification

380V 3N~50Hz

380V 3N~50Hz

Maximum Input Power

31kW

68kW

Maximum Input Current

52A

113A

Refrigerant / Charge Amount

R410A/14.6kg

R410A/13.6kg × 2

Max. Allowable Pressure (Waterside / Refrigerantside)

1.0MPa/4.15MPa

1.0MPa/4.15MPa

Applicable Ambient Temperature

−35℃ ~ 52℃

−35℃ ~ 52℃

Ingress Protection Rating (IP Rating)

IPX4

IPX4

Electric Shock Protection Class

Ⅰ

Ⅰ

Inlet & Outlet Port Size

DN65(Flange)

DN65(Flange)

Waterside Pressure Drop

45kPa

45kPa

Water Flow Rate

11.2m3/h

22.4m3/h

Unit Dimensions

1993 × 960 × 1793mm

2196 × 1216 × 2326mm

Net Weight

620kg

960kg

Noise Level

≤67dB(A)

≤70dB(A)